Trans-ATSAutomatic Transfer Switching ControllersAuthorised access, secure communication
Selectable second language
Log last 50 events & alarm information with measured values
Statistics records
Mains and Generator phase sequence control
Power factor measurement for 3 phases
Active, Reactive, Apparent power measurement
Features | Descriptions |
LCD Languages | English/Chinese, English/Turkish, English/Francais |
Inputs | 6x Configurable digital input |
Outputs | Configurable 2x Relays, 2x Transistors, 1x Remote Start output MBR and GBR outputs |
Current Measurement | 3 phases CT inputs for Load Current, 1x CT input for Earth Current |
Voltage Measurement | 3 phases for Mains, 3 phases for Alternator |
Case | |
Dimensions | 229mm x 152mm x 41mm |
Protection Class | NEMA 4X IP65 at front side |
Operating Range | |
DC Battery Supply range | 8 to 32Vdc, max.operating current is 360mA |
Sender Measurement | |
Cabin.Temp.Measuremet | |
Operating / Storage Temp. | -20°C ... +70°C / -30°C ... +80°C |
Expansions | |
Internal | |
GPRS | with Trans-Messenger.GP module |
Embedded WEB server | with Trans-WEB-AMF module or with Trans-WEB.GP module |
Serial ModBus | with Trans-Messenger.485 module |
Approvals | CE, GOST-R |